Experimental and Numerical Investigation on Air Flow and Temperature Distribution under different Geometries of Displacement Ventilation Devices in an Office Room

by Muna Hameed Al Tuarihi, Ala'a Abbas Mahdi
International Journal of Computer Applications
Foundation of Computer Science (FCS), NY, USA
Volume 169 - Number 4
Year of Publication: 2017
Authors: Muna Hameed Al Tuarihi, Ala'a Abbas Mahdi
10.5120/ijca2017914652

Muna Hameed Al Tuarihi, Ala'a Abbas Mahdi . Experimental and Numerical Investigation on Air Flow and Temperature Distribution under different Geometries of Displacement Ventilation Devices in an Office Room. International Journal of Computer Applications. 169, 4 ( Jul 2017), 15-26. DOI=10.5120/ijca2017914652

@article{ 10.5120/ijca2017914652,
author = { Muna Hameed Al Tuarihi, Ala'a Abbas Mahdi },
title = { Experimental and Numerical Investigation on Air Flow and Temperature Distribution under different Geometries of Displacement Ventilation Devices in an Office Room },
journal = { International Journal of Computer Applications },
issue_date = { Jul 2017 },
volume = { 169 },
number = { 4 },
month = { Jul },
year = { 2017 },
issn = { 0975-8887 },
pages = { 15-26 },
numpages = {9},
url = { https://ijcaonline.org/archives/volume169/number4/27973-2017914652/ },
doi = { 10.5120/ijca2017914652 },
publisher = {Foundation of Computer Science (FCS), NY, USA},
address = {New York, USA}
}
%0 Journal Article
%1 2024-02-07T00:16:27.873693+05:30
%A Muna Hameed Al Tuarihi
%A Ala'a Abbas Mahdi
%T Experimental and Numerical Investigation on Air Flow and Temperature Distribution under different Geometries of Displacement Ventilation Devices in an Office Room
%J International Journal of Computer Applications
%@ 0975-8887
%V 169
%N 4
%P 15-26
%D 2017
%I Foundation of Computer Science (FCS), NY, USA
Abstract

Room air distributions are intended to achieve the required thermal comfort and ventilation for space occupants and processes. The type of air supply diffuser , the type and situation of return grille in the room may affect in the room air distribution and human thermal comfort. In this study three types of air supply diffusers (three direction-square air supply diffuser, one direction-square air supply diffuser and semi-circle air supply diffuser) were used separately as a supply air terminal with one return air grille. The control on the behavior of the air distribution in the enclosed space was very complex. One approach to achieve an optimal control was done by modeling the distribution of air. The tested room was built and meshes by Ansys Fluent14Users guide program. Realizable, k-ε turbulence model was evaluated in predicting the airflow pattern and thermal behavior of DV devices in an office room according to different geometries of displacement ventilation devices. A comparison between both results obtained from experimental work and data of numerical analysis indicated a good agreement between these results due to Iraqi cooling code and ASHRAE standards and according to values of Air Diffusion Performance Index (ADPI) and Effectiveness temperature (ɛt) . The three direction-square diffuser was the best type compared with the others two types since it gives(66.76 %) and(1.82) respectively , and the semi-circle type gives (62.3) % and (1.55) respectively .Also the measured of relative humidity gives approximated converged values between all the three devices.

References
  1. H.B. Awbi Measurement and calculation of the neutral height in a room with displacement ventilation, Building and Environment 37, A Department of Engineering Science, University of Oxford, Oxford, UK 2002Heywood J. Internal combustion engine fundamentals. McGraw-Hill, 1988.
  2. T.K.Arimipanahi, The air distribution index as an indication of consuming Energy and ventilation systems performance, Journal of the Human-Environmental System .Vol. 11; No. 2: 77–84, 2008.
  3. Ting Yao, Numerical Study Of The Effect Of Air Terminal Layouts On The Performance Of Stratum Ventilation System, International High Performance Buildings, Conference School of Mechanical Engineering,2014.
  4. Yukihiro Hashimoto, Numerical investigation on airflow in an office room with a displacement ventilation system, Ninth International IBPSA Conference ,Montréal, Canada, August 15-18, 2005.
  5. isup Lee, Comparison of airflow and pollutant distributions in rooms with traditional displacement ventilation and under-floor air distribution systems, ASHRAE Transactions, 115 ,2009.
  6. Price engineer’s HVAC Handbook, “Engineering guide displacement ventilation, www.price-hvac.com, 2014.
  7. Brohus, H. “Personal exposure to contaminant sources in ventilated rooms”,PhD thesis, Aalborg,University, Aalborg, Denmark. 1997.
  8. Chen, Q. & Glicksman, L. “system performance evaluation and design guidelines for displacement ventilation”, ASHRAE, Atlanta,PP:112,2003.
  9. Qasim H. ,Numerical Study of Air Velocity and Temperature Distribution by Displacement Ventilation,M.SC ,thesis,2014.
  10. H.B. Awbi, “Ventilation of Buildings”, Taylor and Francis group, second edition,2003.
  11. Abdul-Jabar M. Ahmed, “Regional Airflow Characteristics in Mechanically Ventilated Rooms”, M.Sc. Thesis, University of Technology, 2004.
  12. M.Cehlin, Measurements of air temperatures close to a low-velocity diffuser in displacement ventilation using an infrared camera, Energy and Buildings 34,2002.
Index Terms

Computer Science
Information Sciences

Keywords

Displacement ventilation Air supply diffuser return air grille CFD air distribution relative humidity.