Boiler Furnace Pressure Excursion and Set Points

by Poonam Tanwar, B.S. Tanwar
International Journal of Computer Applications
Foundation of Computer Science (FCS), NY, USA
Volume 1 - Number 12
Year of Publication: 2010
Authors: Poonam Tanwar, B.S. Tanwar
10.5120/269-429

Poonam Tanwar, B.S. Tanwar . Boiler Furnace Pressure Excursion and Set Points. International Journal of Computer Applications. 1, 12 ( February 2010), 14-16. DOI=10.5120/269-429

@article{ 10.5120/269-429,
author = { Poonam Tanwar, B.S. Tanwar },
title = { Boiler Furnace Pressure Excursion and Set Points },
journal = { International Journal of Computer Applications },
issue_date = { February 2010 },
volume = { 1 },
number = { 12 },
month = { February },
year = { 2010 },
issn = { 0975-8887 },
pages = { 14-16 },
numpages = {9},
url = { https://ijcaonline.org/archives/volume1/number12/269-429/ },
doi = { 10.5120/269-429 },
publisher = {Foundation of Computer Science (FCS), NY, USA},
address = {New York, USA}
}
%0 Journal Article
%1 2024-02-06T19:46:12.453459+05:30
%A Poonam Tanwar
%A B.S. Tanwar
%T Boiler Furnace Pressure Excursion and Set Points
%J International Journal of Computer Applications
%@ 0975-8887
%V 1
%N 12
%P 14-16
%D 2010
%I Foundation of Computer Science (FCS), NY, USA
Abstract

There are many important parameters to be monitored during any Power plant normal & emergency operations. Furnace pressure is one such very important parameter, which needs continuous control, protection & monitoring against any furnace explosion and implosion. The National Fire Protection Association (NFPA) codes, such as NFPA 85: Boiler and Combustion Systems Hazards Code are dedicated to fire and furnace explosion and implosion protection. The NFPA also requires some additional logic for the furnace pressure control loop to ensure adequate operating safety margins. There should be high and low furnace pressure logic to block the ID fan from increasing or decreasing speed, as is appropriate. A high furnace pressure signal the fan should be blocked from decreasing speed and on a low furnace pressure signal it should be blocked from increasing speed. A main fuel trip (MFT) there should be MFT kicker logic. An MFT occurs when the burner management system detects a dangerous condition and shuts down the boiler by securing the fuel per NFPA and boiler manufacturer requirements. This paper describe the Furnace explosion , Implosions, Furnace pressure set points, cause and remedies in Coal Based Utility Boiler keeping NFPA-8502 standard into consideration[2,5].

References
  1. A reference book on steam generator and emission control-ALSTOM Clean Combustion Technologies, Fifth Edition
  2. M/s NTPC Tanda Project (4x110 MW) site visit and Retrofit project execution in year 2008-09
  3. M/s HINDALCO Industries-RPD (2x278 TPH) site visit and Retrofit project execution in year 2004-05.
  4. M/s APGENCO Boiler visit after furnace excursion in year 2003-2004.
  5. ALSTOM Power Inc. (Formerly known as Combustion Engineering USA), reference documents and learning from various projects.
Index Terms

Computer Science
Information Sciences

Keywords

MFT-Master Fuel Trip